KPM169x Series
 
KPM169x - BIPOLAR INSULATION GUARD FOR NON-GROUNDED DC NETWORKS  KPM169x
  • Direct connection 12 to 48 VDC systems, up to 1600VDC with RH adapter
    (up to 5000VDC on request)
  • Precision reading unaffected of system voltage
  • All inputs and outputs fully isolated
  • Triple-zone insulation monitoring and Supervision relay
  • “Pathfinder” Indicates polarity of dominant earth fault
  • Response time: 125-165mS
  • Analogue output proportional to meter reading (F/L-version)
Description
The digitally controlled KPM169x monitors insulation level between a non-grounded (IT) battery or live DC network and its protective earth.

Only ONE KPM169x can be connected to the same DC-system. An AC or DC (standard)  auxiliary voltage is required for the unit. A green LED indicates AUX POWER on. Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay). In this way false tripping during power up, caused by initial charging of network spread capacitance, is avoided.

The DIN96 front-of-panel mounted instrument reads the insulation level directly in kΩ. The meter has reflection free glass. The ohmmeter and the triple-zone status LEDs at a glance gives the clear safety message:
  • ALARM
  • WARNING
  • HEALTHY
General
SEV MEASURING PRINCIPLE
Insulation is measured between the complete galvanically interconnected DC network and its protective earth. The signal flows to ground via the path of the insulation fault, the level of flow expresses the insulation resistance, the direction of flow expresses the fault polarity. The measuring accuracy is not influenced by any normal kind of load attached to the network. The detection time for an insulation fault is 125-165mS.
 
PATHFINDER/POLARITY FUNCTION
During a Warning or Alarm condition the Polarity LED indicates the polarity causing the trip:
  • POSITIVE EARTH FAULT: LED not lit
  • NEGATIVE EARTH FAULT: blue LED lit
RELAY OUTPUTS
The unit has non-latching C/O relay outputs for Warning (R1), Alarm (R2) and System Error (R3). The Alarm and error relays are fail to safety configured. A trip LED flashes when the trip level is passed, the relay trips after elapsed delay. The timer resets if the fault is removed during countdown. Trip levels and delays are settable on unit rear. Recommended trip level settings will depend on application and priority of safety hazards.

ANALOGUE OUTPUT
All F and L versions have an isolated analogue output proportional to meter reading.
 
SYSTEM SUPERVISION
If voltage of the monitored DC system not connected to the unit input or is to low, the NEG POLARITY LED will flash red, and relay 3 (System Error) will trip. If polarity of the input connection reversed, the NEG POLARITY LED will flash red and blue, and relay 3 will trip. Trip of relay 3 will inhibit operation of the warning and alarm relay and their respective trip LEDs.

SAFETY
When the Voltage Adapter is connected to the instrument, max output from RHx adapters is 60VDC.
 
Description
KPM169x models for 9- 60VDCKPM169x
Scale range: 0-100kΩ - ∞ (>100kΩ)
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

Direct connection for 12, 24 or 48VDC systems.

Models:
KPM169E & KPM169F
KPM169G & KPM169GF
KPM169EH & KPM169EF
KPM169GH & KPM169GFH
 
KPM169x models for 60-200VDC
Scale range: <10-5MΩ
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

This unit use the voltage adapter RH2 for voltage from 60V to max.200VDC.

Models:
KPM169K2 & KPM169L2
KPM169GK2 & KPM169GL2
KPM169K2N & KPM169L2N
KPM169GK2N & KPM169GL2N

KPM169x models for 200-400VDC
Scale range: <10-5MΩ
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

This unit use the voltage adapter RH4 for voltage systems from 200V to max. 400VDC.

Models:
KPM169K4 & KPM169L4
KPM169GK4 & KPM169GL4
KPM169K4N & KPM169L4N
KPM169GK4N & KPM169GL4N

KPM169x models for 400-800VDC
Scale range: <10-5MΩ
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

This unit use the voltage adapter RH8 for voltage systems from 400V to max. 800VDC.

Models:
KPM169K8 & KPM169L8
KPM169GK8 & KPM169GL8
KPM169K8N & KPM169L8N
KPM169GK8N & KPM169GL8N

KPM169x models for 800-1200VDC
Scale range: <10-5MΩ
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

This unit use the voltage adapter RH12 for voltage systems from 800V to max. 1200VDC.

Models:
KPM169K128 & KPM169L12
KPM169GK12 & KPM169GL12
KPM169K12N & KPM169L12N
KPM169GK12N & KPM169GL12N


KPM169x models for 1200-1600VDC
Scale range: <10-5MΩ
These units are used for industrial, marine and offshore installations.
Start of monitoring function is delayed when auxiliary power is switched on (default 2 secs delay).

This unit use the voltage adapter RH16 for voltage systems from 1200V to max. 1600VDC.

Models:

KPM169K16 & KPM169L16
KPM169GK16 & KPM169GL16
KPM169K16N & KPM169L16N
KPM169GK16N & KPM169GL16N