- Three phase Current Protection with VATOR, Definite time or Two
level O/C trip function
- "PREDICTOR" function, The Blackout Preventer
- "Pathfinder" function eases fault finding
- Independent ammeter with Full Load Current (FLC) mark on
scale
- Triple relay operation gives more flexibility
- Built-in fast analogue Amp or Hz transducer (Optional)
Application
The digitally controlled true RMS measurement on the KEC115x provides
precision (1,0%) three phase current protection for AC generators,
motors, transformers etc. for alarms or tripping of a non-essential load
or breaker. It can also be supplied with a built-in current (KEC116x)
or frequency transducer (KEC117x).
The independent class 1,5 moving iron ammeter input (term. 26 & 27)
MUST be externally connected or switched to read individual phase
currents.
User settable trip levels and delays. LEDs flash during countdown and
indicate the alarm status. The "Pathfinder" function identifies the
phase causing the trip by the flashing pattern of the LED.
KEC115x is the standard range with relay outputs for overcurrent and short circuit current trip. The highest phase current will activate the OC/SC levels.
KEC116x range also include a fast response (<50mS) built-in Current transducer
proportional to the HIGHEST phase current signal. This may be used as
an input to a control system, to detect abnormal current conditions
(loss of excitation etc).
KEC117x range also include a fast response (<50mS) built-in frequency transducer. This may be used as an input to a control system.
VATOR (
VAriable
Time
Overcurrent
Release function)
Versions with VATOR function have definite trip time up to 150%
generator over current load. Between 150-200% the trip time will be
reduced dynamically based on a calculated curve to maintain thermal
capability protection and selective protection between parallelled
generators.
Refer to the VATOR calculation excel sheet for further details of the time release curve.
PREDICTOR
The main feature of the Predictor function is to open bus-tie breakers
or trip heavy loads to prevent a total blackout situation. The predictor
relay(s) trips at set over current (O/C) or short circuit current (S/C)
level, prior to the generator breaker trip. If the overload condition
is still present after this load reduction the generator breaker will
trip 1sec or 200mS later relative to set O/C or S/C time delays.
The combination of VATOR and Predictor is the ultimate solution for
electrical selectivity and thermal protection of parallelled generators.
PATHFINDER
The Pathfinder indicates the phase causing an over current or short circuit trip by the flashing pattern of the relevant LED.
Unit meets IEC60092-504 and relevant environmental and EMC tests
specified in IEC60068/60092 and IEC61000/60533 respectively, to comply
with Classification Societies requirements.
Description
KEC115E - KEC116E - KEC117x - Short Circuit and Over Current VATOR Guard
O/C VATOR and definite time S/C trip delays maintain discrimination
between parallelled generators. The fail-safe relay R3 (O/C & S/C)
should be used to open the generator breaker. R1 (S/C) and R2 (O/C) can
be used for local indication, alarm system or PM-System etc. All relays
latch after trip.
KEC115E2 - KEC116E2 - KEC117E2 - Short Circuit and Over Current VATOR Guard
O/C VATOR and definite time S/C trip delays. R2 (O/C) and the fail-safe
relay R1 (S/C) should be used to open the generator breaker. The common
alarm relay R3 (S/C & O/C) can be used for local indication, alarm
system or PM-System etc. All relays latch after trip.
KEC115F - KEC116F - KEC117F - Short Circuit and Over Current Guard
Replaces the classic KEC115. Definite time O/C and S/C trip
delays. Fail-safe S/C relay. All relays latch after trip. Either R1
(S/C) and R2 (O/C) can be used to trip generator breaker with R3 as a
common alarm or R3 can trip the generator breaker with R1/R2 used for local indication, PMS or alarm system input etc.
KEC115F2 - KEC116F2 - KEC117F2 - Short Circuit and Over Current Guard
Definite time O/C and S/C trip delays. Either R1 (S/C) and R2 (O/C)
can be used to trip generator breaker with R3 as a common alarm or
R3 can trip the generator breaker with R1/R2 used for local indication,
PMS or alarm system input etc. NON fail- safe latching relays. Since
all relays are NON fail-safe this version is only suitable as a
replacement for older installations.
KEC115G - KEC116G - KEC117G - Short Circuit and Over Current Guard
For marine emergency/harbour generator sets. Definite time
O/C and S/C trip delays. Non-latching O/C trip relay (R2) and
non-failsafe S/C trip relay (R1). If an engine is set as an emergency
generator only R1 (S/C) shall be used to open the generator breaker as
per the requirements of classification societies. In harbour operation
both relay R1 and R2 shall open the breaker. R3 operates on both S/C and
O/C and can be used for alarm system input etc.
KEC115H - KEC116H - KEC117H - Short Circuit and 2-level Over Current Predictor Guard
2-level O/C settings. Definite time O/C and S/C trip delays.
Instead of the VATOR function the H-versions have 2 over current set
trip levels to reduce trip time in high over load situations.
"Predictor" early action on relays R1 and R2, both relays will trip
after full set O/C or S/C time. R3 is delayed and will trip after full set O/C time + 1sec or
S/C time + 200mS. R3 is used to open the generator breaker. R1 or R2
are used for bus-tie breaker opening or for preference load tripping.
KEC115H4 - KEC116H4 - KEC117H4 - Short Circuit and 2-level Over Current Guard
2-level O/C settings. Definite time O/C and S/C trip delays.
Instead of the VATOR function the H-versions have two over current set
trip levels to reduce trip time in high over load situations. All relays
will trip after full set time. Individual alarm relay outputs give
flexibility for a variety of applications.
KEC115H5 - KEC116H5 - KEC117H5 - Short Circuit and 2-level Over Current Predictor Guard
2-level O/C settings. Definite time O/C trip delays. "Predictor"
early action on R1 and R2 , both relays will trip after full set O/C or S/C time. R3 is delayed and will trip after full set O/C time + 1sec or S/C time + 200mS. R3 is used to open the breaker. R1 is used for bus-tie breaker opening or for preference load tripping.
KEC115P - KEC116P - KEC117P - Short Circuit, VATOR Over Current and Predictor Guard
The best choice for diesel electric systems to prevent totally
black out. VATOR O/C trip delay. Fail safe and latching R3. "Predictor"
early action on relays R1 and R2, R2 will trip after full set O/C and
R1 after full set S/C time. R3 is delayed and will trip after full set
O/C time + 1sec or S/C time + 200mS. R3 is used to open the generator
breaker. R1 and/or R2 are used for bus tie breaker opening, preference
load tripping, PMS or alarm system input etc.
KEC115P2 - KEC116P2 - KEC117P2 - Short Circuit and Over Current Predictor Guard
Definite time O/C and S/C trip delays. Fail safe and latching R3.
"Predictor" early action on relays R1 and R2, both relays will trip
after full set O/C or S/C time. R3 is delayed and will trip after full
set O/C time + 1sec or S/C time + 200mS. R3 is used to open the
generator breaker. R1 and/or R2 are used for bus tie breaker opening,
preference load tripping, PMS or alarm system input etc.
KEC115P3 - KEC116P3 - KEC117P3 - Short Circuit and Over Current Predictor Guard (S/C only)
Definite time O/C and S/C trip delays. Fail safe and latching R3.
"Predictor" early action on relay R1 and R2, both relays will trip after
full set S/C time. R3 is delayed and will trip after full set O/C time +
1sec or S/C time + 200mS. R3 is used to open the generator breaker. R1
and R2 are used for bus tie breaker opening, preference load tripping,
PMS or alarm system input etc.